Schneider Electric 140CPS11400 Modicon Quantum Power Supply Module
The Schneider Electric 140CPS11400, also cataloged as the 140CPS11400 Standalone Power Supply, operates as a dedicated hardware component for converting line AC power into regulated logic DC backplane power within Modicon Quantum automation platforms.
Hardware Specifications
| Parameter |
Specification |
| Model |
140CPS11400 |
| Brand |
Schneider Electric |
| Series |
Modicon Quantum Automation Platform |
| Product Type |
Standalone AC Power Supply Module |
| Input Voltage |
115 VAC / 230 VAC (85 to 264 VAC range) |
| Input Frequency |
47 to 63 Hz |
| Output Voltage |
5.1 VDC (Backplane Bus Power) |
| Output Current |
11 A Continuous |
| Power Rating |
56 W |
| Inrush Current |
30 A at 115 VAC / 60 A at 230 VAC |
| Galvanic Isolation |
1500 VAC Input-to-Backplane / 2300 VAC Input-to-Ground |
| Operating Temp |
0 to 60 deg C |
| Net Weight |
0.65 kg |
| Shipping Weight |
1.2 kg |
Channel Isolation and Process Interface Features
The Schneider Electric 140CPS11400 power supply provides regulated 5.1 VDC power directly to the Modicon Quantum backplane to drive CPU modules, I/O racks, and communication adapters. Integrated overvoltage, overcurrent, and short-circuit protection circuits safeguard internal backplane electronics against grid transients. The power module features 1500 VAC galvanic isolation between input mains and backplane logic to isolate control processing circuits from field ground loops and electrical line noise.
Frequently Asked Questions
Q: Can the 140CPS11400 power supply be used in redundant power configurations?
A: No, the 140CPS11400 is a standalone power supply module. Redundant power configurations require sum-bus or redundant-capable models (such as the 140CPS12400 or 140CPS22400).
Q: How do you configure the input voltage selection on the 140CPS11400 module?
A: The module features an autoranging wide-input power stage (85 to 264 VAC), requiring no manual jumper settings or voltage switch selection for 115 VAC or 230 VAC nominal inputs.
Field Installation Guidelines
-
Confirm that the incoming AC supply voltage matches the operating range of 85 to 264 VAC before wiring power leads.
-
Ensure backplane power is completely isolated before inserting or seating the power supply module into the leftmost rack slot (Slot 1 or Slot 2 depending on backplane model).
-
Seat the module firmly onto the backplane bus connector and tighten the top and bottom retaining screws to ensure solid ground continuity.
-
Connect line, neutral, and protective earth (PE) wiring to the removable terminal block, torquing screws to 0.5 N m.
-
Apply input power and check that the front panel PWR OK LED illuminates steady green to signal healthy 5.1 VDC backplane bus output.
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...