Part Number:
1606-XLS240-UPS
-
Manufacturer:
Allen-Bradley
-
Condition:
Brand New & in Stock
-
Product Type:
Bulletin 1606 Switched Mode Power Supplies
-
Origin:
USA
-
Shipping Detail:
Fedex and UPS etc
-
Warranty:
12 months
Frequently inquire Together
-
Vendor: Allen-Bradley
Allen Bradley 81000-199-51-R Voltage Feedback Board
-
Vendor: Allen-Bradley
1769SC-IF4IH | AB | Spectrum Controls 4 Channel Analog Input Module
-
Vendor: Allen-Bradley
Allen-Bradley 1771-WS Weigh Scale Module
-
Vendor: Allen-Bradley
1784-CF64 | Allen-Bradley | Industrial CompactFlash Card
100% Genuine Stock, 24/7 Service
InquiryTechnical Specifications for Rockwell Automation 1606-XLS240-UPS:
Input:
- Nominal Voltage: 24V DC
-
Voltage Ranges:
- Continuous Operation: 22.5 to 30V DC (see Fig. 5-1)
- Temporarily Allowed: 30 to 35V DC (no damage to the DC-UPS)
- Absolute Maximum: 35V DC (no damage to the DC-UPS)
- Buffer Mode Activation: 0 to 22.5V DC (if the input was above the turn-on level and all buffer conditions are fulfilled)
-
Allowed Input Voltage Ripple:
- <400Hz Bandwidth: Max. 1.5Vpp
- 400Hz to 1kHz Bandwidth: Max. 1Vpp
- Allowed Voltage Between Input and Earth (Ground): Max. 60V DC or 42.4V AC
-
Turn-on Voltage:
- Typical: 22.8V DC (the output does not switch on if the input voltage does not exceed this level)
- Maximum: 23V DC
-
Input Current:
- Internal Current Consumption (Typical): 120mA
- Battery Charging (Typical): 1.1A (constant current mode at 24V input, see Fig. 8-2)
Output in Normal Mode:
- Nominal Voltage: 24V DC (follows the input voltage reduced by the input to output voltage drop)
-
Voltage Drop Between Input and Output:
- Maximum: 0.3V at 10A output current (see Fig. 6-1 for typical values)
- Maximum: 0.45V at 15A output current (see Fig. 6-1 for typical values)
- Ripple and Noise Voltage: Max. 20mVpp (20Hz to 20MHz, 50 Ohm)
- Nominal Current: 15A (continuously allowed)
- Nominal Power: 360W (continuously allowed)
-
Short-Circuit Current:
- Minimum: 17.9A (load impedance 100mOhm, see Fig. 6-2 for typical values)
- Maximum: 21A (load impedance 100mOhm, see Fig. 6-2 for typical values)
Environmental:
- Operating Temperature Range: -25°C to +70°C
- Derating: 0.43A/°C from +60°C to +70°C (normal mode)
- Dimensions: 49mm (W) x 124mm (H) x 117mm (D)
-
Buffer Time (at 10A):
- Typical: 6 minutes 45 seconds with a 7Ah battery module
- Typical: 55 minutes with a 26Ah battery module
Is our price competitive?
What is the warranty period?
What payment methods do we accept?
What is the warranty period?
What shipping methods do we use?
What is our delivery time?
How do we package the goods?
How can customers contact us and request a quote?
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...
Contact Information
- Email: sales7@cambia.cn
- TEL: +86 180 3027 3592