Allen-Bradley 22F-A2P5N103 PowerFlex 4M AC Drive
The Allen-Bradley 22F-A2P5N103, also cataloged as the 22F-A2P5N103 AC Drive, operates as a dedicated hardware component for feed-through motor speed modulation and pulse-width modulated (PWM) inverter control within PowerFlex 4M automation networks.
Hardware Specifications
| Parameter |
Specification |
| Model |
22F-A2P5N103 |
| Brand |
Allen-Bradley |
| Origin |
USA / Multi-Region |
| Weight |
1.6 kg (3.5 lb) |
| Dimensions |
72.0 x 174.0 x 136.0 mm (2.83 x 6.85 x 5.35 in) |
| Operating Temp |
-10 deg C to 50 deg C (14 deg F to 122 deg F) |
| Power Consumption |
0.37 kW (0.5 HP) power output rating |
| Input Voltage |
240 VAC, 1-Phase (200-240 VAC range, 50/60 Hz) |
| Output Voltage |
0 to 230 VAC, 3-Phase variable frequency |
| Output Current |
2.5 Amps |
| Enclosure Rating |
IP20 / NEMA Open Type (Frame Size A) |
| Control Interface |
Integral LED display with fixed digital keypad |
| Embedded I/O |
5 Discrete Inputs (24 VDC), 2 Analog Inputs (0-10V, 4-20mA), 1 Relay Output |
Deterministic Backplane & I/O Density Scaling
The PowerFlex 4M architecture integrates high-density drive control circuitry with feed-through wiring topology, simplifying physical terminal management inside compact enclosures. Internal microprocessor-driven pulse-width modulation (PWM) algorithms execute deterministic speed control across 3-phase induction motors. Digital input density is optimized via DIP-switch selectable 24 VDC Sink or Source logic modes, ensuring millisecond-level feedback response over Modbus RTU serial networks without increasing physical enclosure volume.
Frequently Asked Questions
Q: Does the 22F-A2P5N103 drive feature an embedded dynamic braking transistor (IGBT)?
A: No. The '3' suffix code specifies a base drive configuration constructed without an internal dynamic braking IGBT.
Q: How are analog input references wired and controlled on the physical terminal block?
A: The drive provides two isolated analog input terminals (0 to 10 VDC voltage and 4 to 20 mA current), allowing simultaneous connection of external speed potentiometers or process controllers.
Q: What mounting restrictions apply to the Frame Size A IP20 enclosure?
A: The unit is designed for direct DIN-rail or panel mounting within protective industrial control cabinets, requiring uninhibited vertical airflow channels for natural thermal convection.
Field Installation Guidelines
-
Mount the Frame Size A drive vertically on a standard 35 mm DIN rail or panel surface, maintaining a minimum clearance of 120 mm (4.7 in) above and below the chassis to enable unobstructed convective heat dissipation.
-
Wire the single-phase 240 VAC input source to terminals L1 and L2 using copper conductors rated for 75 deg C, ensuring motor output leads (U, V, W) connect directly to 3-phase motor load terminals.
-
Route analog signal wires (0-10V / 4-20 mA) in separate shielded cables, terminating cable shields to the drive functional ground point to minimize electro-magnetic noise coupling.
-
Ground the drive enclosure chassis by securing a heavy gauge copper conductor directly from the ground terminal to the main panel enclosure ground bus bar to ensure EMC compliance and surge protection.
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...