Allen Bradley 1734-OE2V Analog Output Module
The Allen Bradley 1734-OE2V, part of the Bulletin 1734 Point I/O series, operates as a compact, high-density analog voltage output module designed for distributed control applications. It provides two single-ended output channels capable of driving field actuators, control valves, and variable frequency drives (VFDs) with high precision over standard voltage control loops.
Hardware Specifications
| Parameter |
Specification |
| Model |
1734-OE2V |
| Brand |
Allen Bradley (Rockwell Automation) |
| Product Series |
Point I/O (Bul. 1734) |
| Component Type |
Fieldbus I/O Analog Output Module |
| Number of Analog Outputs |
2 single-ended channels |
| Analog Output Voltage Ranges |
0 to 10 VDC, -10 to +10 VDC |
| Output Resolution |
14 bits (signed) |
| Module Power Supply |
24 VDC |
| Operating Temperature |
-20 deg C to +55 deg C |
| Storage Temperature |
-40 deg C to +85 deg C |
| Relative Humidity |
5% to 95% non-condensing |
Distributed Signal Processing & Point I/O Architecture
The 1734-OE2V converts 14-bit signed digital values from the host controller into proportional analog voltage signals. Designed to snap directly onto a 1734 wiring base (such as the 1734-TB or 1734-TBS), the module communicates with the primary programmable automation controller (PAC) via a Point I/O bus interface adapter (e.g., 1734-AENT or 1734-PDN). Key features include:
-
Configurable Output Ranges: Software-selectable range configuration per channel (0 to 10 VDC or bipolar -10 to +10 VDC) without physical jumper changes.
-
Onboard Diagnostics: LED indicators provide immediate status for module health, bus communication, and channel activity.
-
Hot-Swappable Architecture: Supports Removal and Insertion Under Power (RIUP), enabling module replacement without interrupting adjacent Point I/O modules on the DIN rail.
Frequently Asked Questions
Q: Can channels on the 1734-OE2V be individually configured for different voltage ranges?
A: Yes, each of the 2 single-ended channels can be independently configured in Studio 5000 / RSLogix 5000 software to operate in either 0 to 10 VDC or -10 to +10 VDC mode.
Q: What wiring bases are compatible with the 1734-OE2V module?
A: The module is compatible with standard Bulletin 1734 terminal bases, including the 1734-TB, 1734-TBS, 1734-TOP, and 1734-TOPS bases.
Field Installation Guidelines
-
Mount the 1734 terminal base securely onto a grounded 35 mm DIN rail before snapping the 1734-OE2V module into place.
-
Set the mechanical keying switch on the terminal base to the designated position for voltage output modules to prevent accidental insertion of incorrect module types.
-
Route analog signal wiring using shielded, twisted-pair cable to minimize electrical noise interference on 0-10V loop signals.
-
Ensure proper grounding by landing the cable shield at a single end (typically at the panel ground bar) rather than floating or grounding at both ends.
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...