Allen-Bradley 1794-AND FLEX I/O DeviceNet Adaptor Module
The Allen-Bradley 1794-AND (1794-AND DeviceNet Adaptor Module) serves as the primary 1794-AND DeviceNet Adaptor Module utilized to execute distributed I/O communication across FLEX I/O platforms. The module provides a DeviceNet network interface between field-mounted FLEX I/O assemblies and higher-level controllers, supporting deterministic data exchange through CAN-based DeviceNet infrastructure.
Hardware Specifications
| Parameter |
Specification |
| Model |
1794-AND |
| Brand |
Allen-Bradley |
| Product Type |
DeviceNet Adaptor Module |
| Series |
FLEX I/O |
| Network Protocol |
DeviceNet |
| Network Technology |
CAN-Based Communication |
| I/O Capacity |
Up to 8 FLEX I/O Modules |
| Baud Rates |
125 Kbps, 250 Kbps, 500 Kbps |
| Node Address Range |
00 to 63 |
| Address Configuration |
Hardware Thumbwheel Switches |
| Nominal Input Voltage |
24 VDC |
| Operating Voltage Range |
19.2 VDC to 31.2 VDC |
| FlexBus Output Current |
640 mA at 5 VDC |
| Power Supply Current Load |
330 mA to 400 mA Maximum |
| Maximum Power Consumption |
7.9 W |
| Maximum Power Dissipation |
4.6 W |
| Isolation Voltage |
850 VDC for 1 s |
| Dimensions |
87 mm x 68 mm x 69 mm |
| Operating Temp |
-20 deg C to +70 deg C |
| Enclosure Rating |
IP20 Open Type |
| Mounting Method |
35 mm DIN Rail or Panel Mount |
| Hazardous Location Rating |
Class I Division 2, Zone 2 Ex ec IIC T4 Gc |
DeviceNet Network and FLEX I/O Integration
The 1794-AND functions as the communication gateway between DeviceNet networks and FLEX I/O field assemblies. The module exchanges cyclic and diagnostic data with connected I/O modules while presenting a unified network node to the supervisory controller.
Support for up to eight FLEX I/O modules allows distributed installation of input and output hardware near field equipment, reducing field wiring requirements and cabinet complexity. Network communication parameters are configurable through DeviceNet services or hardware address switches depending on system requirements.
Deterministic DeviceNet Communication
The DeviceNet interface supports selectable communication rates of 125 Kbps, 250 Kbps, and 500 Kbps. Node addressing is established through integrated thumbwheel switches, allowing physical assignment of network addresses from 00 through 63.
The adaptor supplies FlexBus logic power to connected FLEX I/O modules and coordinates data transfer between field devices and the network master. Isolation between user power and internal circuitry assists in protecting communication electronics from field-side electrical disturbances.
Frequently Asked Questions
Q: How many FLEX I/O modules can be connected to the 1794-AND?
A: The adaptor supports up to eight FLEX I/O modules on a single FLEX I/O rack.
Q: Which DeviceNet communication speeds are supported?
A: The module supports 125 Kbps, 250 Kbps, and 500 Kbps DeviceNet baud rates.
Q: How is the DeviceNet node address configured?
A: Node addresses from 00 to 63 are assigned using integrated hardware thumbwheel switches.
Field Installation Guidelines
-
Set the node address before applying power.
-
Verify DeviceNet baud rate matches the network configuration.
-
Use approved DeviceNet cabling and termination practices.
-
Mount on a 35 mm DIN rail or approved panel surface.
-
Confirm FlexBus current requirements before adding I/O modules.
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...