GE DS200TCDAG1BDB Digital I/O Board
Configured for discrete‑signal processing in Mark V LM control networks, the GE DS200TCDAG1BDB (DS200TCDAG1BDB digital I/O board) provides contact‑input acquisition from DTBA/DTBB terminal boards and contact‑output routing to TCRA relay/solenoid drivers through IONet‑based communication paths.
Hardware Specifications
| Parameter |
Specification |
| Model |
DS200TCDAG1BDB |
| Brand |
General Electric |
| Origin |
United States |
| Weight |
Not specified |
| Dimensions |
15.9 cm high x 17.8 cm |
| Operating Temp |
-30 to +65 deg C |
| Power Requirements |
+5 V dc, 6 A |
| Product Type |
Digital I/O Board |
| Series |
Mark V LM |
| Relay Channels |
12 |
| Supply Voltage |
28 V dc |
| Mounting |
DIN‑rail |
| Technology |
Surface‑mount |
| Manual |
GEI‑100182B |
Profinet / EtherNet/IP Deterministic Networks
Although TCDA communicates through IONet rather than Profinet/EtherNet/IP, its behavior aligns with deterministic scan cycles typical of GE Speedtronic architectures. The board’s IONet ID, termination, and stall‑timer functions are jumper‑configured, ensuring predictable timing for discrete‑signal propagation. I/O density scaling is maintained across R1/R2/R5 cores, with TCDA acting as the primary interface between DTBA/DTBB contact inputs and TCRA relay outputs. Firmware flash compatibility resides at the controller level; TCDA itself provides fixed electrical behavior with configurable jumpers only.
Frequently Asked Questions
Q: What is the primary function of DS200TCDAG1BDB? A: It processes digital contact inputs from DTBA/DTBB boards and routes relay/solenoid outputs to TCRA boards through IONet.
Q: Can TCDA be hot‑swapped? A: No. The board must be replaced only when the associated core is de‑energized to avoid undefined IONet states.
Q: What do jumpers J4–J6 configure? A: They set the board’s IONet ID, ensuring proper addressing within the Mark V LM I/O network.
Field Installation Guidelines
- Mount the board on its DIN‑rail carrier within the designated digital I/O core.
- Verify jumper settings (J1–J8) according to system configuration before energizing.
- Ensure JP, JQ, JR, JO1, JO2, JX1, and JX2 connectors are fully seated and strain‑relieved.
- Route shielded twisted‑pair cabling for IONet connections to minimize noise.
- After installation, validate contact‑input transitions and relay‑output behavior through TCQC diagnostics.
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...