GE EPSCPE100-ABAC Standalone PACSystems Controller
Configured for logic execution, distributed I/O management, and industrial network communications in PACSystems control architectures, the GE EPSCPE100-ABAC (EPSCPE100 Standalone PACSystems Controller) provides direct processing, protocol handling, and deterministic control functions within PACSystems RSTi-EP platforms. The controller integrates CPU resources, Ethernet networking, serial communications, and field I/O management into a compact standalone control node.
Hardware Specifications
| Parameter |
Specification |
| Model |
EPSCPE100-ABAC |
| Brand |
GE |
| Product Type |
Standalone PACSystems Controller |
| Processor |
1 GHz Industrial CPU |
| User Memory |
1.0 MB Non-Volatile Memory |
| Maximum Discrete I/O |
2,048 points |
| Maximum Analog I/O |
32k Words |
| MTBF |
Greater than 100,000 hours |
| Ethernet Ports |
4 x 10/100 Mbps Ethernet Interfaces |
| LAN Architecture |
1 dedicated LAN port, 1 internally switched 3-port LAN |
| Serial Ports |
1 x RS-232, 1 x RS-485 |
| Supported Protocols |
PROFINET, Modbus TCP/IP, OPC UA Server, SRTP Client/Server, EtherNet/IP |
| Network Redundancy |
PROFINET System Redundancy, MRP |
| Programming Software |
Proficy Machine Edition (PME) |
| Programming Languages |
Ladder Logic, Structured Text, C# |
| Power Input |
24 VDC |
| Power Architecture |
Dual Internal Power Paths |
| Environmental Protection |
Conformal Coated PCB |
| Storage Temp |
-40 deg C to 70 deg C |
| Dimensions |
3.5 cm x 13 cm x 13.5 cm |
Profinet Deterministic Networks and I/O Scaling
The EPSCPE100-ABAC supports deterministic industrial Ethernet communications through PROFINET networking services. The controller can manage distributed I/O architectures while maintaining synchronized data exchange with connected field devices and remote I/O stations.
With support for up to 2,048 discrete I/O points and 32k words of analog data, the controller provides scalable deployment within machine control and process automation applications. PROFINET system redundancy and Media Redundancy Protocol (MRP) functions support network availability strategies for fault-tolerant installations.
Frequently Asked Questions
Q: How many Ethernet interfaces are integrated into the controller?
A: The controller includes four 10/100 Mbps Ethernet interfaces consisting of one dedicated LAN port and one internally switched three-port LAN segment.
Q: Which industrial protocols are supported?
A: Supported protocols include PROFINET, Modbus TCP/IP, OPC UA Server, SRTP Client/Server, and EtherNet/IP.
Q: What programming environments are supported?
A: The controller is programmed using Proficy Machine Edition (PME) and supports Ladder Logic, Structured Text, and C# application development.
Field Installation Guidelines
-
Install the controller in accordance with PACSystems RSTi-EP mounting requirements.
-
Provide a stable 24 VDC power source before commissioning.
-
Utilize separate network segments where required for control and supervisory traffic.
-
Verify PROFINET device names and network addressing before system startup.
-
Route Ethernet and serial communication cables separately from high-voltage power conductors.
-
Maintain enclosure environmental conditions suitable for industrial electronic equipment.
-
Confirm firmware compatibility across connected I/O modules and engineering tools.
-
Perform communication verification and I/O validation before placing the control system into operation.
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...