Honeywell CC-PAIN01 51410069-175 Analog Input Module
Configured for analog current-signal acquisition in Honeywell Series C architectures, the Honeywell CC-PAIN01 51410069-175 (CC-PAIN01 Analog Input Module) provides direct measurement of field transmitter signals within Experion PKS platforms. The module supports sixteen single-ended input channels, 4-20 mA current inputs, 16-bit conversion resolution, and integrated field-power protection for process measurement applications.
Hardware Specifications
| Parameter |
Specification |
| Model |
CC-PAIN01 |
| Brand |
Honeywell |
| Part Number |
51410069-175 |
| Product Type |
Analog Input Module |
| Series |
Honeywell Series C |
| Origin |
USA |
| Dimensions |
152.4 mm x 61 mm x 20.3 mm |
| Weight |
Approx. 0.37 kg |
| Operating Temp |
0 deg C to +60 deg C |
| Protective Coating |
G3 conformal coating |
| Power Consumption |
150 mA at 24 VDC |
| Input Channels |
16 single-ended channels |
| Input Signal Type |
Current input |
| Input Range |
4-20 mA |
| A/D Resolution |
16-bit |
| Scan Rate |
50 ms |
| Accuracy @ 23.5 deg C +/-2 deg C |
+/-0.075% FSR |
| Accuracy @ 0 to 60 deg C |
+/-0.15% FSR |
| CMRR |
70 dB |
| NMRR |
20 dB at 60 Hz |
| Channel Crosstalk |
-60 dB |
| Input Protection |
+/-30 V maximum input |
| Filter Type |
Single-pole RC filter |
| Filter Response |
-3 dB at 6.0 Hz |
| Supported Transmitters |
2-wire and self-powered transmitters |
| Field Power Protection |
Integrated non-incendive current limiting |
Channel-to-Channel Isolation and Signal Integrity
The CC-PAIN01 acquires low-level process measurements through sixteen analog current-input channels. The module incorporates precision 200 Ohm input sampling circuitry, 16-bit analog-to-digital conversion, and integrated filtering to support stable process data acquisition.
Signal conditioning circuitry provides common-mode noise rejection and channel separation performance suitable for industrial environments. The specified crosstalk performance of -60 dB and common-mode rejection of 70 dB assist in maintaining signal integrity when multiple process loops are installed within the same cabinet infrastructure.
Frequently Asked Questions
Q: What signal type is accepted by the CC-PAIN01?
A: The module is designed for standard 4-20 mA analog current-loop inputs from 2-wire or self-powered transmitters.
Q: What conversion resolution does the module provide?
A: The integrated analog-to-digital converter provides 16-bit resolution.
Q: Can the module be installed in redundant architectures?
A: Yes. The module supports redundant installation using the CC-TAIN11 IOTA, while CC-TAIN01 is used for non-redundant configurations.
Field Installation Guidelines
-
De-energize the I/O cabinet before installing the module.
-
Verify compatibility with the corresponding CC-TAIN01 or CC-TAIN11 IOTA.
-
Route analog signal cables separately from power conductors.
-
Maintain cable shield grounding according to site standards.
-
Confirm transmitter loop polarity before energization.
-
Verify channel readings and scaling during commissioning.
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...