The technical specifications for the Schneider Electric 140AVO02000 analog output module from the Modicon Quantum series:
-
Number of Channels: 4
-
Bus Current: 700 mA
-
Power Dissipation: 4.5 W (maximum)
-
I/O Map: 4 output words
-
Wiring Length: Up to 400 meters (1312.34 feet)
-
Resolution: 12 bits
-
Analog Output Range:
- Bipolar Voltage: ±10 V (for ≥1000 Ohm load)
- Bipolar Voltage: ±5 V (for ≥500 Ohm load)
- Unipolar Voltage (0-10 V): ≥1000 Ohm load
- Unipolar Voltage (0-5 V): ≥500 Ohm load
-
Source Resistance: 0.1 Ohm
-
Absolute Accuracy Error: ±0.15% of full scale at 77°F (25°C)
-
Linearity: ±1 LSB
-
Accuracy Drift with Temperature:
- Unipolar: 0.003% of full scale/°C
- Bipolar: 0.004% of full scale/°C
- Maximum Unipolar: 0.005% of full scale/°C
- Maximum Bipolar: 0.007% of full scale/°C
-
Isolation Between Channels: 500 V for 1 minute (47-63 Hz AC)
-
Isolation Between Channels and Bus: 780 V for 1 minute (AC)
-
Update Time: 3 ms
-
Setting Time: 700 µs to ±0.1% of the final value (maximum)
-
Bus Current Requirement: 700 mA
-
Associated Fuse Rating: 0.063 mA (3 AG fast blow, 250 V)
-
Local Signaling:
- External Fault: 1 green LED (active)
- Channel Turned On: 1 red LED
- Channel Fault: 4 green LEDs
-
Net Weight: 0.66 lb (0.3 kg)
-
Operating Temperature Range: 32-140°F (0-60°C)
-
Storage Temperature Range: -40-185°F (-40-85°C)
-
Relative Humidity: 95% (without condensation)
-
Operating Altitude: ≤16404.2 ft (5000 m)
-
Certifications: FM Class 1 Division 2, cUL, UL 508, CSA C22.2 No 142
-
Resistance to Electromagnetic Fields: 9.14 V/m (10 V/m) at 80-2000 MHz (IEC 801-3)
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...
Contact Information