ABB 1MRK002305-AAr01 Time Synchronization Module
Configured for precise sub-microsecond time stamping and system-wide clock alignment in ABB Relion 670 series Intelligent Electronic Devices (IEDs), the ABB 1MRK002305-AAr01 (1MRK002305-AAr01 Time Synchronization Module) provides direct physical/electrical execution.
Hardware Specifications
| Parameter |
Specification |
| Model |
1MRK002305-AAr01 |
| Brand |
ABB |
| Origin |
Sweden |
| Weight |
1.52 kg (3.35 lbs) |
| Dimensions |
Standard Relion 670 rear card slot form factor |
| Operating Temp |
-40 to +85 deg C (-40 to +185 deg F) |
| Humidity |
5% to 95% non-condensing |
| Ingress Protection |
IP20 |
| Supply Voltage |
24 VDC (internal backplane rail) |
| Input Signals |
IRIG-B time code formats (001, 002, 100) |
| Output Signals |
1PPS (Pulse-per-second), 10 MHz, NTP/SNTP distribution |
| Synchronization Accuracy |
Up to +/- 100 ns |
| System Compatibility |
ABB Relion 670 Series (e.g., REx670 V1.1) |
Substation Time Synchronization and Phasor Measurement Execution
Protection relays and Synchrophasor / Phasor Measurement Units (PMUs) require microsecond-level time synchronization across widespread transmission grids to enable synchronized fault recording and power system vector analysis. The 1MRK002305-AAr01 receives external IRIG-B time signals from master GPS clocks and converts them into internal 1PPS and 10 MHz timing pulses with an accuracy of up to ±100 ns. This ultra-precise clocking allows Relion 670 IEDs to accurately timestamp sequence-of-events (SOE) logs and sync sampled values across wide-area protection networks.
Frequently Asked Questions
Q: What IRIG-B signal formats are supported by the 1MRK002305-AAr01 module?
A: The module supports standard BCD-encoded IRIG-B signals, including formats 001, 002, and 100, delivered via BNC coaxial or optical fiber inputs depending on the chassis terminal layout.
Q: Can this module distribute time synchronization to other internal cards within the same Relion 670 chassis?
A: Yes. Once the 1MRK002305-AAr01 locks onto an external IRIG-B source, it drives high-precision timing signals across the backplane bus to synchronize binary input timestamping and analog sampling hardware across all installed cards.
Field Installation Guidelines
-
Isolate auxiliary station supply power and external tripping loops prior to inserting or servicing cards inside the Relion 670 sub-rack.
-
Put on a grounded Electrostatic Discharge (ESD) wrist strap before removing the module from its anti-static shielding bag.
-
Insert the module into its assigned card slot on the rear of the Relion 670 IED chassis, pushing firmly along the side guides until fully connected.
-
Tighten the upper and lower front-panel retaining screws to 0.6 Nm to ensure secure mechanical grounding and EMC shielding integrity.
-
Attach the incoming IRIG-B cable from the master clock to the module input connector, verifying signal polarity and signal strength before powering on the IED.
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...
Contact Information