InquiryModel AAI141 (16-channel, Non-Isolated)
-
Input Signal:
- 4 to 20 mA DC
- 1 to 5 V DC (allowable common mode voltage ±1 V or less)
- Allowable Input Current/Voltage: 27 mA
-
Input Resistance:
- Power ON: 400 Ω (at 20 mA) to 1000 Ω (at 4 mA)
- Power OFF: 500 kΩ or larger
- Accuracy: ±16 µA
- Data Update Period: 10 ms
- Step Response Time: 100 ms
- Transmitter Power Supply: 14.8 V or higher (at 20 mA), 26.4 V or less (at 0 mA)
- Drift due to Ambient Temperature Change: ±16 µA/10 °C
- Maximum Current Consumption: 310 mA (5 V DC), 450 mA (24 V DC)
- Weight: 0.2 kg
- External Connection: Pressure clamp terminal, KS cable, MIL connector cable
- HART Communication: Available
Is our price competitive?
What is the warranty period?
What payment methods do we accept?
What is the warranty period?
What shipping methods do we use?
What is our delivery time?
How do we package the goods?
How can customers contact us and request a quote?
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...