GE STXPNS001 RSTi ProfiNet Slave Network Adapter
The GE STXPNS001, also cataloged as the STXPNS001 RSTi ProfiNet Slave Network Adapter, operates as a dedicated hardware component for distributed I/O communication within PROFINET industrial Ethernet networks. The adapter functions as a PROFINET slave device, providing deterministic data exchange between RSTi slice I/O modules and supervisory PLC or PAC controllers through integrated Ethernet switching architecture.
Hardware Specifications
| Parameter |
Specification |
| Model |
STXPNS001 |
| Brand |
GE |
| Product Type |
PROFINET Slave Network Adapter |
| Network Protocol |
PROFINET Slave |
| Data Transfer Rate |
100 Mbps Full Duplex |
| Maximum Expansion Modules |
Up to 32 RSTi I/O slice modules including termination module |
| Input Data Capacity |
128 bytes |
| Output Data Capacity |
128 bytes |
| System Power Input |
24 VDC nominal |
| Input Voltage Range |
11 VDC to 28.8 VDC |
| Internal Current Consumption |
70 mA maximum at 24 VDC |
| Internal Bus Power Supply |
1.0 A maximum at 5 VDC |
| Field Power Contacts |
10.0 A maximum |
| Ethernet Ports |
2 x RJ-45 |
| Switch Type |
Integrated 2-port Ethernet switch |
| Network Topology |
Line or Star |
| Configuration Method |
GSDML file configuration |
| Mounting |
DIN rail |
| Operating Temp |
0 deg C to 55 deg C |
| Storage Temp |
-20 deg C to 70 deg C |
| Relative Humidity |
5% to 90%, non-condensing |
| Origin |
United States |
Profinet Deterministic Networks and I/O Density Scaling
The STXPNS001 serves as the communication gateway between a PROFINET controller and distributed RSTi I/O assemblies. Operating at 100 Mbps full-duplex Ethernet speed, the adapter exchanges cyclic process data while supporting deterministic network performance required for industrial automation applications.
The module supports expansion of up to 32 connected RSTi slice I/O modules, including the termination module. This architecture enables incremental I/O density scaling without modification of the network interface structure. Configuration is performed through standard PROFINET engineering environments using GSDML device descriptions.
Frequently Asked Questions
Q: How many RSTi modules can be connected to the STXPNS001?
A: The adapter supports up to 32 RSTi slice modules, including the required termination module.
Q: Does the adapter support MRP ring redundancy?
A: No. Available specifications indicate support for line and star topologies only and do not support MRP ring topology operation.
Q: What process data capacity is available?
A: The adapter supports up to 128 bytes of input data and 128 bytes of output data for cyclic PROFINET communication.
Field Installation Guidelines
-
Mount the adapter securely on a compatible DIN rail before attaching expansion I/O modules.
-
Install the termination module at the end of the slice I/O assembly.
-
Verify the 24 VDC supply remains within the specified 11 VDC to 28.8 VDC operating range.
-
Use industrial Ethernet cabling suitable for PROFINET communication environments.
-
Configure the device using the appropriate GSDML file within the PLC engineering software.
-
Maintain physical separation between Ethernet cabling and high-voltage power wiring.
-
Verify network device naming and IP addressing before commissioning.
-
Confirm correct I/O mapping and cyclic data exchange after startup.
Topbrands PLC Limited is a top supplier of genuine new PLC and DCS parts, serving over 50 countries globally. We offer high-quality products from renowned brands like Bently Nevada, Honeywell, ABB, and more. With our warehouse in China stocking up to 30,000 pieces, we ensure rapid delivery to meet urgent order needs while maintaining competitive pricing to save our customers' budgets. Learn more...